Appendix
Bar graph read-out
This function is used to select whether the bar graph should
follow the analog output or the level read-out.
Changes will not have influence on the relay settings.
Shuttle
®
reverts to normal read-out.
Note: If the mA settings are inverted (the level reference
at 4 mA is set higher than the level reference at
20 mA), the bar graph will increase when the level
decreases and vice versa.
The bargraph follows the analog output.
The bar graph follows the level read-out.
Note: If the active measuring range has been decreased
to e.g. 1,45 - 3 m (see next page), the range of
the bar graph will be changed accordingly (all seg-
ments lit at 3 m and all segments off at 1,45 m.)
The bar graph is deactivated.